Transformers MCQs 2026
88 questions with detailed answers · 31 from past papers · 9 quiz batches available
Choose a Quiz Batch. Each batch has 10 questions from this topic, in order. Take them one by one to work through all 88 MCQs. Login to save your scores and see your best per batch.
Read each question, think about the answer, then click Show Answer to reveal the correct option and explanation. Load 10 at a time so it stays manageable — perfect for one-topic study sessions on the bus or during a break.
- Q1 easy
Primary purpose of an isolation transformer is to
💡 Explanation:It separates equipment from supply ground, reducing shock hazard and noise coupling.
- Q2 Past Paper · PPSC/FPSC/CSS easy
The EMF induced in a transformer primary winding is given by the equation
💡 Explanation:The RMS induced EMF per phase equals 4.44 times frequency, number of turns, and maximum flux in webers.
- Q3 Past Paper · PPSC/FPSC/CSS medium
Maximum flux Φm in a transformer core is directly proportional to
💡 Explanation:From E = 4.44 f N Φm, for fixed N, Φm ∝ V/f, which is why flux must be limited at low frequency.
- Q4 easy
The turns ratio of an ideal transformer is defined as
💡 Explanation:Turns ratio a = Np/Ns relates primary and secondary voltages and currents inversely.
- Q5 Past Paper · PPSC/FPSC/CSS easy
For an ideal transformer, if primary has 1000 turns and secondary has 100 turns, the turns ratio is
💡 Explanation:a = Np/Ns = 1000/100 = 10, meaning primary voltage is ten times secondary voltage.
- Q6 easy
In an ideal step-down transformer, the secondary current compared to primary current is
💡 Explanation:Power conservation gives VpIp = VsIs, so lower secondary voltage means higher secondary current.
- Q7 Past Paper · PPSC/FPSC/CSS easy
The voltage ratio of an ideal transformer equals
💡 Explanation:Vp/Vs = Np/Ns for an ideal transformer with same flux linking both windings.
- Q8 Past Paper · PPSC/FPSC/CSS medium
Open-circuit (OC) test on a transformer is performed on the
💡 Explanation:OC test uses rated voltage on LV side while HV is open, keeping test voltage safely accessible.
- Q9 medium
The open-circuit test of a transformer primarily determines
💡 Explanation:At no load, copper loss is negligible; measured input gives iron loss and magnetizing parameters.
- Q10 Past Paper · PPSC/FPSC/CSS medium
Short-circuit (SC) test on a transformer is normally conducted on the
💡 Explanation:Reduced voltage (5-10% rated) is applied to HV with LV shorted to measure impedance and copper loss.
- Q11 medium
The short-circuit test of a transformer is used to determine
💡 Explanation:Rated current flows at reduced voltage; iron loss is small and copper loss dominates.
- Q12 Past Paper · PPSC/FPSC/CSS easy
During OC test, wattmeter reading represents mainly
💡 Explanation:No-load current is small, so copper loss is negligible compared to constant core losses.
- Q13 medium
During SC test, the applied voltage is approximately
💡 Explanation:Short-circuit impedance limits current to rated value at a small fraction of rated voltage.
- Q14 Past Paper · PPSC/FPSC/CSS medium
All-day efficiency of a distribution transformer is also called
💡 Explanation:It considers energy losses over 24 hours at varying load cycles, not just one load point.
- Q15 easy
An auto-transformer differs from a two-winding transformer because
💡 Explanation:Part of the winding is common, reducing copper and size for same voltage ratio.
- Q16 Past Paper · PPSC/FPSC/CSS hard
Savings in copper of an auto-transformer compared to two-winding type is approximately
💡 Explanation:Common winding carries only the difference current, saving conductor material.
- Q17 medium
Auto-transformers are NOT used when
💡 Explanation:Shared winding provides no electrical isolation between primary and secondary.
- Q18 Past Paper · PPSC/FPSC/CSS easy
An isolation transformer has turns ratio of
💡 Explanation:Isolation transformers typically have equal turns to transfer voltage while isolating circuits.
- Q19 Past Paper · PPSC/FPSC/CSS easy
A current transformer (CT) is connected in
💡 Explanation:CT primary carries line current; secondary feeds measuring instruments with stepped-down current.
- Q20 easy
Standard secondary current of most instrument CTs is
💡 Explanation:Industry standardizes on 5 A (or 1 A) secondary for ammeters, relays, and energy meters.
- Q21 Past Paper · PPSC/FPSC/CSS easy
A potential transformer (PT) is connected in
💡 Explanation:PT steps down high voltage to standard 110 V or 100 V for metering and protection.
- Q22 Past Paper · PPSC/FPSC/CSS medium
The secondary of a CT must never be
💡 Explanation:Open secondary with primary energized causes dangerous overvoltage due to magnetizing flux buildup.
- Q23 easy
CT ratio 200/5 means secondary current of 5 A when primary carries
💡 Explanation:Ratio expresses primary to secondary current transformation for measurement scaling.
- Q24 medium
Per-unit system for transformers uses base quantities such that
💡 Explanation:pu = actual value / base value; bases chosen for convenient calculation on common MVA and kV.
- Q25 Past Paper · PPSC/FPSC/CSS hard
Base impedance in per-unit system is given by
💡 Explanation:Zbase = V²/S in consistent units (e.g., kV and MVA) for per-unit impedance conversion.
- Q26 hard
Transformer per-unit impedance is independent of
💡 Explanation:When properly referred, Zpu is the same whether calculated on HV or LV side.
- Q27 medium
Hysteresis loss in transformer core depends on
💡 Explanation:Ph ∝ f × Bmax^n (Steinmetz); hysteresis varies with flux density and frequency.
- Q28 Past Paper · PPSC/FPSC/CSS hard
Eddy current loss in transformer laminations varies approximately with
💡 Explanation:Pe ∝ f² × B² × t² for thin laminations, rising sharply with flux and frequency.
- Q29 medium
Stacking laminations reduces eddy current loss because
💡 Explanation:Thinner laminations confine eddy currents to small loops, reducing I²R eddy loss.
- Q30 Past Paper · PPSC/FPSC/CSS easy
The no-load current of a power transformer is typically
💡 Explanation:Mostly magnetizing component; small compared to rated current in large power transformers.
- Q31 easy
Silica gel breather in a transformer prevents
💡 Explanation:Silica gel absorbs moisture from air drawn into conservator during oil contraction.
- Q32 Past Paper · PPSC/FPSC/CSS medium
Conservator tank on a transformer maintains
💡 Explanation:Oil expands/contracts with temperature; conservator allows breathing without exposing oil to air.
- Q33 easy
Transformers are rated in
💡 Explanation:Rating is apparent power because load power factor is unknown; losses depend on current not PF alone.
- Q34 Past Paper · PPSC/FPSC/CSS easy
Iron losses in a transformer are
💡 Explanation:Core flux remains near rated value at normal operation, so Pi stays essentially constant.
- Q35 easy
Copper losses in a transformer vary as
💡 Explanation:Pc = I²R; at x per unit load, Pc = x² × full-load copper loss.
- Q36 Past Paper · PPSC/FPSC/CSS hard
Equivalent resistance referred to secondary equals
💡 Explanation:Primary resistance referred to secondary is scaled by inverse turns ratio squared.
- Q37 medium
A welding transformer is designed for
💡 Explanation:High leakage reactance limits short-circuit current and provides stable arc voltage.
- Q38 hard
Pulse transformer design emphasizes
💡 Explanation:Signal integrity requires minimal leakage L and distributed capacitance for sharp pulses.
- Q39 hard
Three-phase transformer vector group Dy11 means
💡 Explanation:Dy11: secondary line voltage leads primary by 30° (clock position 11 = −30° from 12).
- Q40 hard
Vector group Yd1 indicates phase displacement of
💡 Explanation:Clock number 1 means secondary leads primary by 30° in positive sequence.
- Q41 medium
Parallel operation of Yy0 and Dd0 transformers is
💡 Explanation:Different phase shifts cause large circulating currents even if voltage ratios match.
- Q42 easy
Commercial efficiency of a transformer is defined at
💡 Explanation:Commercial efficiency = output at full load / (output + losses at full load), used for rating comparisons.
- Q43 Past Paper · PPSC/FPSC/CSS medium
Maximum efficiency of a transformer occurs when
💡 Explanation:Total loss Pt = Pi + Pc×(x)²; minimum when dPt/dx = 0 gives x = √(Pi/Pc), i.e., Cu loss = iron loss.
- Q44 hard
If iron loss is 2 kW and full-load copper loss is 8 kW, load fraction for maximum efficiency is
💡 Explanation:x = √(Pi/Pc) = √(2/8) = √(0.25) = 0.5 or 50% load.
- Q45 Past Paper · PPSC/FPSC/CSS easy
At maximum efficiency, the variable copper loss equals
💡 Explanation:This is the fundamental condition for minimum total loss at a given load fraction.
- Q46 medium
A transformer has Pi = 1 kW and Pc = 4 kW. Maximum efficiency occurs at
💡 Explanation:x = √(1/4) = 0.5, so maximum efficiency is at half rated load.
- Q47 Past Paper · PPSC/FPSC/CSS medium
Star-star (Y-Y) connection of three-phase transformers gives
💡 Explanation:Y-Y connection preserves phase sequence with no inherent angular displacement.
- Q48 medium
Delta-delta (Δ-Δ) connection is preferred when
💡 Explanation:Open-delta operation allows continued two-phase service at reduced capacity using two transformers.
- Q49 Past Paper · PPSC/FPSC/CSS medium
Star-delta (Y-Δ) connection introduces a phase shift of
💡 Explanation:Y-Δ shifts secondary voltage by 30° relative to primary, important for parallel operation.
- Q50 hard
Delta-star (Δ-Y) connection produces a phase shift of
💡 Explanation:Δ-Y is the mirror of Y-Δ; secondary leads primary by 30 electrical degrees.
- Q51 Past Paper · PPSC/FPSC/CSS medium
Scott connection uses two transformers to convert
💡 Explanation:Scott T-connection provides balanced two-phase supply from a three-phase source.
- Q52 hard
In Scott connection, one transformer is called teaser and has
💡 Explanation:Teaser transformer winding is tapped at 86.6% (√3/2 × 50%) to obtain 90° displacement.
- Q53 Past Paper · PPSC/FPSC/CSS easy
ONAN cooling classification means
💡 Explanation:ONAN relies on natural oil circulation and natural air cooling without pumps or fans.
- Q54 easy
OFAF cooling in transformers stands for
💡 Explanation:OFAF uses oil pumps and forced air fans for higher capacity heat removal.
- Q55 Past Paper · PPSC/FPSC/CSS easy
As transformer load increases, voltage regulation generally
💡 Explanation:Greater load current causes larger resistive and reactive drops, worsening regulation.
- Q56 medium
Voltage regulation of a transformer is defined as
💡 Explanation:Regulation measures percentage drop in secondary terminal voltage from no-load to full-load.
- Q57 Past Paper · PPSC/FPSC/CSS hard
Negative voltage regulation in a transformer can occur when
💡 Explanation:Leading PF can cause voltage rise at terminals, giving negative regulation.
- Q58 medium
The approximate equivalent circuit of a transformer is referred to
💡 Explanation:Parameters are referred to one winding for simplified analysis using turns ratio.
- Q59 Past Paper · PPSC/FPSC/CSS medium
In the exact equivalent circuit, R0 and X0 represent
💡 Explanation:Parallel branch R0-X0 accounts for iron loss and magnetizing reactance.
- Q60 medium
Series components R1 and X1 in transformer equivalent circuit represent
💡 Explanation:Impedance drop in windings is modeled by series R and X referred to one side.
- Q61 Past Paper · PPSC/FPSC/CSS easy
Buchholz relay is installed in
💡 Explanation:It detects gas accumulation and oil surge from internal faults such as arcing or overheating.
- Q62 medium
Buchholz relay operates on the principle of
💡 Explanation:Decomposing oil releases gas; severe faults displace oil, tripping the relay.
- Q63 Past Paper · PPSC/FPSC/CSS easy
A Buchholz relay provides protection against
💡 Explanation:It gives early warning for winding faults, core overheating, and loss of oil before major damage.
- Q64 medium
On-load tap changer (OLTC) allows
💡 Explanation:OLTC switches taps under load using resistors or reactor transition to maintain voltage.
- Q65 Past Paper · PPSC/FPSC/CSS easy
Off-load tap changer must be operated when
💡 Explanation:De-energizing prevents arcing and ensures safe tap contact change.
- Q66 medium
Leakage flux in a transformer links
💡 Explanation:Leakage flux does not link both windings and causes voltage drop modeled as leakage reactance.
- Q67 medium
Percentage impedance of a transformer indicates
💡 Explanation:Z% = (short-circuit voltage / rated voltage) × 100 at rated current.
- Q68 medium
Two transformers can operate in parallel if they have
💡 Explanation:Mismatch causes circulating current and unequal load sharing.
- Q69 medium
Polarity test of a transformer determines
💡 Explanation:Additive or subtractive polarity affects parallel connection and relay CT connections.
- Q70 hard
Subtractive polarity means
💡 Explanation:Terminals 1-H1 and 2-H2 are on same physical side for subtractive marking.
- Q71 easy
Three single-phase transformers in bank can replace
💡 Explanation:Banking provides flexibility; one unit can be spare or replaced individually.
- Q72 hard
Open-delta connection delivers
💡 Explanation:With one transformer removed, capacity = 1/√3 ≈ 57.7% of complete delta bank rating.
- Q73 hard
Tertiary winding in Y-Y-Δ transformer bank is often
💡 Explanation:Delta tertiary provides path for zero-sequence current and stabilizes tertiary flux unbalance.
- Q74 hard
Zero-sequence impedance of Y-Δ transformer is
💡 Explanation:Delta blocks zero-sequence current from passing to Y primary, giving high Z0.
- Q75 medium
Instrument PT secondary is normally grounded for
💡 Explanation:Grounding prevents dangerous floating potential on metering circuits and provides reference for relays.
- Q76 hard
CT accuracy class 5P20 means
💡 Explanation:Protection class CT maintains specified accuracy up to 20× rated primary for fault currents.
- Q77 medium
Magnetizing inrush current occurs when transformer is
💡 Explanation:Residual flux plus applied flux can saturate core momentarily, drawing large inrush.
- Q78 hard
To reduce switching inrush, transformers may use
💡 Explanation:Point-on-wave switching and pre-insertion resistors limit peak inrush current magnitude.
- Q79 medium
Core saturation during inrush causes
💡 Explanation:Saturated core needs high magnetizing MMF, producing harmonic-rich inrush lasting several cycles.
- Q80 easy
Distribution transformers use
💡 Explanation:They reduce HV distribution to LV utilization voltage at poles or pads.
- Q81 medium
Power transformer impedance is designed mainly for
💡 Explanation:Higher Z% limits short-circuit current but increases voltage regulation trade-off.
- Q82 easy
Transformer oil serves as
💡 Explanation:Mineral oil insulates windings and transfers heat from core and coils to tank walls.
- Q83 medium
Dissolved gas analysis (DGA) in transformers detects
💡 Explanation:Gases like H2, CH4, C2H2 indicate overheating, partial discharge, or arcing in oil/paper.
- Q84 hard
Winding hot-spot temperature limit for oil transformers is typically guided by
💡 Explanation:Hot-spot above 98-110°C accelerates cellulose aging; insulation life halves roughly every 6-7°C rise.
- Q85 medium
FR3 or ester oil in transformers offers
💡 Explanation:Natural ester fluids have fire points above 300°C and are environmentally friendlier.
- Q86 easy
Transformer tank is earthed to
💡 Explanation:Grounding the tank protects personnel and ensures proper operation of protective devices.
- Q87 easy
Lightning arrester on transformer protects against
💡 Explanation:Arresters clamp transient overvoltages from lightning or switching before they damage insulation.
- Q88 hard
Surge impedance loading (SIL) relates to
💡 Explanation:While line-related, transformer-line interface design considers SIL for voltage profile on long lines.