Transformers MCQs 2026

88 questions with detailed answers · 31 from past papers · 9 quiz batches available

📚 Electrical Engineering 📄 31 Past-Paper Qs ✓ Free · No Login Needed
🎯 Mock Test

Read each question, think about the answer, then click Show Answer to reveal the correct option and explanation. Load 10 at a time so it stays manageable — perfect for one-topic study sessions on the bus or during a break.

Page 1 of 1 Questions 110 of 88
  1. Q1 easy

    Primary purpose of an isolation transformer is to

    1. A maximize efficiency at 1:10 ratio
    2. B provide galvanic isolation and safety
    3. C eliminate all losses
    4. D increase frequency
    💡 Explanation:

    It separates equipment from supply ground, reducing shock hazard and noise coupling.

  2. Q2 Past Paper · PPSC/FPSC/CSS easy

    The EMF induced in a transformer primary winding is given by the equation

    1. A E = 2π f N Φm
    2. B E = 4.44 f N Φm
    3. C E = 4.44 f N I
    4. D E = f N Φm
    💡 Explanation:

    The RMS induced EMF per phase equals 4.44 times frequency, number of turns, and maximum flux in webers.

  3. Q3 Past Paper · PPSC/FPSC/CSS medium

    Maximum flux Φm in a transformer core is directly proportional to

    1. A current and turns
    2. B frequency squared
    3. C applied voltage and inversely proportional to frequency
    4. D core area only
    💡 Explanation:

    From E = 4.44 f N Φm, for fixed N, Φm ∝ V/f, which is why flux must be limited at low frequency.

  4. Q4 easy

    The turns ratio of an ideal transformer is defined as

    1. A Ns/Np
    2. B Vp/Is
    3. C Ep × Is
    4. D Np/Ns
    💡 Explanation:

    Turns ratio a = Np/Ns relates primary and secondary voltages and currents inversely.

  5. Q5 Past Paper · PPSC/FPSC/CSS easy

    For an ideal transformer, if primary has 1000 turns and secondary has 100 turns, the turns ratio is

    1. A 0.1
    2. B 10
    3. C 100
    4. D 100000
    💡 Explanation:

    a = Np/Ns = 1000/100 = 10, meaning primary voltage is ten times secondary voltage.

  6. Q6 easy

    In an ideal step-down transformer, the secondary current compared to primary current is

    1. A higher
    2. B lower
    3. C equal
    4. D zero
    💡 Explanation:

    Power conservation gives VpIp = VsIs, so lower secondary voltage means higher secondary current.

  7. Q7 Past Paper · PPSC/FPSC/CSS easy

    The voltage ratio of an ideal transformer equals

    1. A inverse of turns ratio squared
    2. B turns ratio
    3. C square of turns ratio
    4. D independent of turns
    💡 Explanation:

    Vp/Vs = Np/Ns for an ideal transformer with same flux linking both windings.

  8. Q8 Past Paper · PPSC/FPSC/CSS medium

    Open-circuit (OC) test on a transformer is performed on the

    1. A low-voltage winding
    2. B high-voltage winding
    3. C both windings simultaneously
    4. D tertiary winding only
    💡 Explanation:

    OC test uses rated voltage on LV side while HV is open, keeping test voltage safely accessible.

  9. Q9 medium

    The open-circuit test of a transformer primarily determines

    1. A copper losses
    2. B full-load efficiency only
    3. C short-circuit impedance
    4. D core (iron) losses and no-load current
    💡 Explanation:

    At no load, copper loss is negligible; measured input gives iron loss and magnetizing parameters.

  10. Q10 Past Paper · PPSC/FPSC/CSS medium

    Short-circuit (SC) test on a transformer is normally conducted on the

    1. A low-voltage winding
    2. B neutral winding
    3. C high-voltage winding
    4. D open secondary
    💡 Explanation:

    Reduced voltage (5-10% rated) is applied to HV with LV shorted to measure impedance and copper loss.

  11. Q11 medium

    The short-circuit test of a transformer is used to determine

    1. A iron losses
    2. B copper losses and equivalent impedance
    3. C turns ratio
    4. D no-load power factor
    💡 Explanation:

    Rated current flows at reduced voltage; iron loss is small and copper loss dominates.

  12. Q12 Past Paper · PPSC/FPSC/CSS easy

    During OC test, wattmeter reading represents mainly

    1. A I²R copper loss at full load
    2. B dielectric loss only
    3. C stray load loss
    4. D hysteresis and eddy current losses
    💡 Explanation:

    No-load current is small, so copper loss is negligible compared to constant core losses.

  13. Q13 medium

    During SC test, the applied voltage is approximately

    1. A 5 to 10 percent of rated voltage
    2. B 50 percent of rated voltage
    3. C 100 percent of rated voltage
    4. D 0.1 percent of rated voltage
    💡 Explanation:

    Short-circuit impedance limits current to rated value at a small fraction of rated voltage.

  14. Q14 Past Paper · PPSC/FPSC/CSS medium

    All-day efficiency of a distribution transformer is also called

    1. A commercial efficiency
    2. B maximum efficiency
    3. C energy efficiency
    4. D regulation efficiency
    💡 Explanation:

    It considers energy losses over 24 hours at varying load cycles, not just one load point.

  15. Q15 easy

    An auto-transformer differs from a two-winding transformer because

    1. A it has no core
    2. B it cannot step up voltage
    3. C it has no losses
    4. D primary and secondary share a common winding
    💡 Explanation:

    Part of the winding is common, reducing copper and size for same voltage ratio.

  16. Q16 Past Paper · PPSC/FPSC/CSS hard

    Savings in copper of an auto-transformer compared to two-winding type is approximately

    1. A (1 − Vlow/Vhigh) × 100%
    2. B always 50%
    3. C zero always
    4. D twice the rating
    💡 Explanation:

    Common winding carries only the difference current, saving conductor material.

  17. Q17 medium

    Auto-transformers are NOT used when

    1. A economy is important
    2. B small voltage change is needed
    3. C galvanic isolation is required
    4. D starting large motors
    💡 Explanation:

    Shared winding provides no electrical isolation between primary and secondary.

  18. Q18 Past Paper · PPSC/FPSC/CSS easy

    An isolation transformer has turns ratio of

    1. A 10:1
    2. B 1:1
    3. C 1:10
    4. D variable only
    💡 Explanation:

    Isolation transformers typically have equal turns to transfer voltage while isolating circuits.

  19. Q19 Past Paper · PPSC/FPSC/CSS easy

    A current transformer (CT) is connected in

    1. A parallel with the line
    2. B across the bus bar in shunt
    3. C series with the line
    4. D only in neutral ground
    💡 Explanation:

    CT primary carries line current; secondary feeds measuring instruments with stepped-down current.

  20. Q20 easy

    Standard secondary current of most instrument CTs is

    1. A 5 A or 1 A
    2. B 110 V
    3. C 415 V
    4. D 0.1 A only
    💡 Explanation:

    Industry standardizes on 5 A (or 1 A) secondary for ammeters, relays, and energy meters.

  21. Q21 Past Paper · PPSC/FPSC/CSS easy

    A potential transformer (PT) is connected in

    1. A series with load current
    2. B inside transformer tank
    3. C only on secondary of CT
    4. D parallel (shunt) across the line
    💡 Explanation:

    PT steps down high voltage to standard 110 V or 100 V for metering and protection.

  22. Q22 Past Paper · PPSC/FPSC/CSS medium

    The secondary of a CT must never be

    1. A open-circuited on load
    2. B shorted
    3. C grounded
    4. D connected to relay
    💡 Explanation:

    Open secondary with primary energized causes dangerous overvoltage due to magnetizing flux buildup.

  23. Q23 easy

    CT ratio 200/5 means secondary current of 5 A when primary carries

    1. A 5 A
    2. B 2000 A
    3. C 200 A
    4. D 20 A
    💡 Explanation:

    Ratio expresses primary to secondary current transformation for measurement scaling.

  24. Q24 medium

    Per-unit system for transformers uses base quantities such that

    1. A all values are in amperes only
    2. B per-unit values are dimensionless ratios
    3. C per-unit has physical units
    4. D only voltage has per-unit
    💡 Explanation:

    pu = actual value / base value; bases chosen for convenient calculation on common MVA and kV.

  25. Q25 Past Paper · PPSC/FPSC/CSS hard

    Base impedance in per-unit system is given by

    1. A Sbase / Vbase
    2. B Vbase × Ibase²
    3. C Ibase / Vbase
    4. D Vbase² / Sbase
    💡 Explanation:

    Zbase = V²/S in consistent units (e.g., kV and MVA) for per-unit impedance conversion.

  26. Q26 hard

    Transformer per-unit impedance is independent of

    1. A the base MVA
    2. B the turns ratio
    3. C which side it is referred to
    4. D the frequency
    💡 Explanation:

    When properly referred, Zpu is the same whether calculated on HV or LV side.

  27. Q27 medium

    Hysteresis loss in transformer core depends on

    1. A load current only
    2. B maximum flux density and frequency
    3. C secondary voltage squared only
    4. D tap position only
    💡 Explanation:

    Ph ∝ f × Bmax^n (Steinmetz); hysteresis varies with flux density and frequency.

  28. Q28 Past Paper · PPSC/FPSC/CSS hard

    Eddy current loss in transformer laminations varies approximately with

    1. A flux density only
    2. B frequency only
    3. C load power factor
    4. D flux density squared and frequency squared
    💡 Explanation:

    Pe ∝ f² × B² × t² for thin laminations, rising sharply with flux and frequency.

  29. Q29 medium

    Stacking laminations reduces eddy current loss because

    1. A they increase flux density
    2. B they eliminate hysteresis
    3. C thin sheets increase resistance to eddy paths
    4. D they increase core volume
    💡 Explanation:

    Thinner laminations confine eddy currents to small loops, reducing I²R eddy loss.

  30. Q30 Past Paper · PPSC/FPSC/CSS easy

    The no-load current of a power transformer is typically

    1. A 50 to 60 percent
    2. B 2 to 5 percent of rated current
    3. C equal to full-load current
    4. D zero always
    💡 Explanation:

    Mostly magnetizing component; small compared to rated current in large power transformers.

  31. Q31 easy

    Silica gel breather in a transformer prevents

    1. A moisture entering transformer oil
    2. B oil overheating
    3. C short circuit
    4. D phase unbalance
    💡 Explanation:

    Silica gel absorbs moisture from air drawn into conservator during oil contraction.

  32. Q32 Past Paper · PPSC/FPSC/CSS medium

    Conservator tank on a transformer maintains

    1. A secondary voltage constant
    2. B three-phase balance
    3. C zero iron loss
    4. D positive oil pressure and accommodates expansion
    💡 Explanation:

    Oil expands/contracts with temperature; conservator allows breathing without exposing oil to air.

  33. Q33 easy

    Transformers are rated in

    1. A kW only
    2. B kVA or MVA
    3. C kVAR only
    4. D hp only
    💡 Explanation:

    Rating is apparent power because load power factor is unknown; losses depend on current not PF alone.

  34. Q34 Past Paper · PPSC/FPSC/CSS easy

    Iron losses in a transformer are

    1. A constant from no load to full load
    2. B proportional to square of load
    3. C zero at no load
    4. D only at short circuit
    💡 Explanation:

    Core flux remains near rated value at normal operation, so Pi stays essentially constant.

  35. Q35 easy

    Copper losses in a transformer vary as

    1. A load current linearly
    2. B inversely with load
    3. C independent of load
    4. D square of load current
    💡 Explanation:

    Pc = I²R; at x per unit load, Pc = x² × full-load copper loss.

  36. Q36 Past Paper · PPSC/FPSC/CSS hard

    Equivalent resistance referred to secondary equals

    1. A R1 only
    2. B R2 only
    3. C R2 + R1 × (Ns/Np)²
    4. D R1 × Np/Ns
    💡 Explanation:

    Primary resistance referred to secondary is scaled by inverse turns ratio squared.

  37. Q37 medium

    A welding transformer is designed for

    1. A constant voltage like PT
    2. B high drooping volt-ampere characteristic
    3. C 1:1 isolation only
    4. D zero leakage reactance
    💡 Explanation:

    High leakage reactance limits short-circuit current and provides stable arc voltage.

  38. Q38 hard

    Pulse transformer design emphasizes

    1. A high iron loss
    2. B fast rise time and low leakage inductance
    3. C large magnetizing current
    4. D ONAN cooling only
    💡 Explanation:

    Signal integrity requires minimal leakage L and distributed capacitance for sharp pulses.

  39. Q39 hard

    Three-phase transformer vector group Dy11 means

    1. A star primary delta secondary 0°
    2. B delta-delta 30° lag
    3. C star-star 11°
    4. D delta primary, star secondary, 11 o'clock shift (−30°)
    💡 Explanation:

    Dy11: secondary line voltage leads primary by 30° (clock position 11 = −30° from 12).

  40. Q40 hard

    Vector group Yd1 indicates phase displacement of

    1. A −30°
    2. B
    3. C +30° (1 o'clock)
    4. D 180°
    💡 Explanation:

    Clock number 1 means secondary leads primary by 30° in positive sequence.

  41. Q41 medium

    Parallel operation of Yy0 and Dd0 transformers is

    1. A not possible due to phase shift mismatch
    2. B always ideal
    3. C required for Scott
    4. D same as Yd11 parallel
    💡 Explanation:

    Different phase shifts cause large circulating currents even if voltage ratios match.

  42. Q42 easy

    Commercial efficiency of a transformer is defined at

    1. A no load
    2. B full load
    3. C half load only
    4. D quarter load only
    💡 Explanation:

    Commercial efficiency = output at full load / (output + losses at full load), used for rating comparisons.

  43. Q43 Past Paper · PPSC/FPSC/CSS medium

    Maximum efficiency of a transformer occurs when

    1. A copper loss is zero
    2. B iron loss is twice copper loss
    3. C load is zero
    4. D copper loss equals iron loss
    💡 Explanation:

    Total loss Pt = Pi + Pc×(x)²; minimum when dPt/dx = 0 gives x = √(Pi/Pc), i.e., Cu loss = iron loss.

  44. Q44 hard

    If iron loss is 2 kW and full-load copper loss is 8 kW, load fraction for maximum efficiency is

    1. A 0.25
    2. B 1.0
    3. C 0.5
    4. D 0.707
    💡 Explanation:

    x = √(Pi/Pc) = √(2/8) = √(0.25) = 0.5 or 50% load.

  45. Q45 Past Paper · PPSC/FPSC/CSS easy

    At maximum efficiency, the variable copper loss equals

    1. A constant iron loss
    2. B half the iron loss
    3. C twice the iron loss
    4. D zero
    💡 Explanation:

    This is the fundamental condition for minimum total loss at a given load fraction.

  46. Q46 medium

    A transformer has Pi = 1 kW and Pc = 4 kW. Maximum efficiency occurs at

    1. A 50% load
    2. B 25% load
    3. C 100% load
    4. D 75% load
    💡 Explanation:

    x = √(1/4) = 0.5, so maximum efficiency is at half rated load.

  47. Q47 Past Paper · PPSC/FPSC/CSS medium

    Star-star (Y-Y) connection of three-phase transformers gives

    1. A 30° phase shift
    2. B 180° phase shift
    3. C 60° phase shift
    4. D zero phase shift between primary and secondary line voltages
    💡 Explanation:

    Y-Y connection preserves phase sequence with no inherent angular displacement.

  48. Q48 medium

    Delta-delta (Δ-Δ) connection is preferred when

    1. A minimum copper is needed
    2. B phase shift of 30° is required
    3. C one transformer can be removed for maintenance (open delta)
    4. D neutral is mandatory
    💡 Explanation:

    Open-delta operation allows continued two-phase service at reduced capacity using two transformers.

  49. Q49 Past Paper · PPSC/FPSC/CSS medium

    Star-delta (Y-Δ) connection introduces a phase shift of

    1. A
    2. B 30° lagging of secondary
    3. C 60° leading
    4. D 180°
    💡 Explanation:

    Y-Δ shifts secondary voltage by 30° relative to primary, important for parallel operation.

  50. Q50 hard

    Delta-star (Δ-Y) connection produces a phase shift of

    1. A 30° lagging
    2. B
    3. C 30° leading on secondary
    4. D 45°
    💡 Explanation:

    Δ-Y is the mirror of Y-Δ; secondary leads primary by 30 electrical degrees.

  51. Q51 Past Paper · PPSC/FPSC/CSS medium

    Scott connection uses two transformers to convert

    1. A three-phase to two-phase
    2. B single-phase to three-phase
    3. C DC to AC
    4. D two-phase to single-phase only
    💡 Explanation:

    Scott T-connection provides balanced two-phase supply from a three-phase source.

  52. Q52 hard

    In Scott connection, one transformer is called teaser and has

    1. A 100% same rating
    2. B 50% rating
    3. C 173% rating
    4. D 86.6% of main transformer voltage rating
    💡 Explanation:

    Teaser transformer winding is tapped at 86.6% (√3/2 × 50%) to obtain 90° displacement.

  53. Q53 Past Paper · PPSC/FPSC/CSS easy

    ONAN cooling classification means

    1. A Oil Forced Air Forced
    2. B Oil Natural Air Natural
    3. C Oil Natural Air Forced
    4. D Oil Forced Air Natural
    💡 Explanation:

    ONAN relies on natural oil circulation and natural air cooling without pumps or fans.

  54. Q54 easy

    OFAF cooling in transformers stands for

    1. A Oil Natural Air Forced
    2. B Oil Forced Air Natural
    3. C Oil Forced Air Forced
    4. D Oil Free Air Forced
    💡 Explanation:

    OFAF uses oil pumps and forced air fans for higher capacity heat removal.

  55. Q55 Past Paper · PPSC/FPSC/CSS easy

    As transformer load increases, voltage regulation generally

    1. A decreases
    2. B remains constant
    3. C becomes negative always
    4. D increases
    💡 Explanation:

    Greater load current causes larger resistive and reactive drops, worsening regulation.

  56. Q56 medium

    Voltage regulation of a transformer is defined as

    1. A (V2 no-load − V2 full-load) / V2 rated × 100%
    2. B (V2 full-load − V2 no-load) / V2 rated
    3. C V2 full-load / V1
    4. D I2 / I1
    💡 Explanation:

    Regulation measures percentage drop in secondary terminal voltage from no-load to full-load.

  57. Q57 Past Paper · PPSC/FPSC/CSS hard

    Negative voltage regulation in a transformer can occur when

    1. A load is purely resistive
    2. B load power factor is leading
    3. C load power factor is lagging unity
    4. D transformer is open-circuited
    💡 Explanation:

    Leading PF can cause voltage rise at terminals, giving negative regulation.

  58. Q58 medium

    The approximate equivalent circuit of a transformer is referred to

    1. A both sides simultaneously without referral
    2. B the core only
    3. C the tank
    4. D one side (primary or secondary)
    💡 Explanation:

    Parameters are referred to one winding for simplified analysis using turns ratio.

  59. Q59 Past Paper · PPSC/FPSC/CSS medium

    In the exact equivalent circuit, R0 and X0 represent

    1. A series leakage impedance
    2. B load resistance
    3. C no-load (core loss and magnetizing) branch
    4. D tap changer resistance
    💡 Explanation:

    Parallel branch R0-X0 accounts for iron loss and magnetizing reactance.

  60. Q60 medium

    Series components R1 and X1 in transformer equivalent circuit represent

    1. A core loss
    2. B winding resistance and leakage reactance
    3. C magnetizing current
    4. D cooling system
    💡 Explanation:

    Impedance drop in windings is modeled by series R and X referred to one side.

  61. Q61 Past Paper · PPSC/FPSC/CSS easy

    Buchholz relay is installed in

    1. A transformer conservator pipe / main tank pipe
    2. B circuit breaker panel
    3. C secondary bus bar
    4. D lightning arrester
    💡 Explanation:

    It detects gas accumulation and oil surge from internal faults such as arcing or overheating.

  62. Q62 medium

    Buchholz relay operates on the principle of

    1. A gas accumulation and oil flow displacement
    2. B overcurrent in secondary
    3. C overvoltage on primary
    4. D external temperature only
    💡 Explanation:

    Decomposing oil releases gas; severe faults displace oil, tripping the relay.

  63. Q63 Past Paper · PPSC/FPSC/CSS easy

    A Buchholz relay provides protection against

    1. A external line faults only
    2. B lightning on transmission towers
    3. C incipient internal faults
    4. D metering errors
    💡 Explanation:

    It gives early warning for winding faults, core overheating, and loss of oil before major damage.

  64. Q64 medium

    On-load tap changer (OLTC) allows

    1. A only off-load tapping
    2. B frequency change
    3. C phase reversal
    4. D voltage adjustment without interrupting load
    💡 Explanation:

    OLTC switches taps under load using resistors or reactor transition to maintain voltage.

  65. Q65 Past Paper · PPSC/FPSC/CSS easy

    Off-load tap changer must be operated when

    1. A at full rated load
    2. B transformer is de-energized or unloaded
    3. C during short circuit
    4. D only at maximum tap
    💡 Explanation:

    De-energizing prevents arcing and ensures safe tap contact change.

  66. Q66 medium

    Leakage flux in a transformer links

    1. A both windings equally
    2. B neither winding
    3. C only one winding
    4. D only the core
    💡 Explanation:

    Leakage flux does not link both windings and causes voltage drop modeled as leakage reactance.

  67. Q67 medium

    Percentage impedance of a transformer indicates

    1. A iron loss in watts
    2. B no-load current
    3. C turns ratio
    4. D voltage drop at rated current
    💡 Explanation:

    Z% = (short-circuit voltage / rated voltage) × 100 at rated current.

  68. Q68 medium

    Two transformers can operate in parallel if they have

    1. A same voltage ratio, phase shift, percent impedance, and polarity
    2. B different voltage ratios
    3. C opposite polarity only
    4. D any impedance
    💡 Explanation:

    Mismatch causes circulating current and unequal load sharing.

  69. Q69 medium

    Polarity test of a transformer determines

    1. A core material type
    2. B relative direction of induced EMF in windings
    3. C oil dielectric strength
    4. D cooling class
    💡 Explanation:

    Additive or subtractive polarity affects parallel connection and relay CT connections.

  70. Q70 hard

    Subtractive polarity means

    1. A opposite side terminals same polarity
    2. B no polarity exists
    3. C HV and LV terminals on same side have same instantaneous polarity
    4. D only delta connection possible
    💡 Explanation:

    Terminals 1-H1 and 2-H2 are on same physical side for subtractive marking.

  71. Q71 easy

    Three single-phase transformers in bank can replace

    1. A only auto-transformer
    2. B one three-phase transformer
    3. C only Scott connection
    4. D no other configuration
    💡 Explanation:

    Banking provides flexibility; one unit can be spare or replaced individually.

  72. Q72 hard

    Open-delta connection delivers

    1. A 57.7% of full delta-delta capacity
    2. B 100% capacity
    3. C 33% capacity
    4. D 86.6% capacity
    💡 Explanation:

    With one transformer removed, capacity = 1/√3 ≈ 57.7% of complete delta bank rating.

  73. Q73 hard

    Tertiary winding in Y-Y-Δ transformer bank is often

    1. A open circuited always
    2. B used only for metering
    3. C connected to primary only
    4. D delta connected unbalanced load carrier
    💡 Explanation:

    Delta tertiary provides path for zero-sequence current and stabilizes tertiary flux unbalance.

  74. Q74 hard

    Zero-sequence impedance of Y-Δ transformer is

    1. A zero on all sides
    2. B equal to positive sequence
    3. C very high on Y side
    4. D negative value
    💡 Explanation:

    Delta blocks zero-sequence current from passing to Y primary, giving high Z0.

  75. Q75 medium

    Instrument PT secondary is normally grounded for

    1. A increasing voltage
    2. B reducing iron loss
    3. C changing turns ratio
    4. D safety and relay reference
    💡 Explanation:

    Grounding prevents dangerous floating potential on metering circuits and provides reference for relays.

  76. Q76 hard

    CT accuracy class 5P20 means

    1. A 20% error at 5 A
    2. B 5% error up to 20 times rated current
    3. C 5 VA burden only
    4. D 20 kV insulation
    💡 Explanation:

    Protection class CT maintains specified accuracy up to 20× rated primary for fault currents.

  77. Q77 medium

    Magnetizing inrush current occurs when transformer is

    1. A switched on at voltage zero crossing unfavorably
    2. B at full load steady state
    3. C during tap change off load
    4. D with secondary shorted
    💡 Explanation:

    Residual flux plus applied flux can saturate core momentarily, drawing large inrush.

  78. Q78 hard

    To reduce switching inrush, transformers may use

    1. A open secondary permanently
    2. B remove core laminations
    3. C increase frequency only
    4. D controlled switching or series resistance
    💡 Explanation:

    Point-on-wave switching and pre-insertion resistors limit peak inrush current magnitude.

  79. Q79 medium

    Core saturation during inrush causes

    1. A large magnetizing current with harmonics
    2. B zero current
    3. C only fundamental at rated value
    4. D decreased iron loss
    💡 Explanation:

    Saturated core needs high magnetizing MMF, producing harmonic-rich inrush lasting several cycles.

  80. Q80 easy

    Distribution transformers use

    1. A only step-up for generation
    2. B only isolation 1:1
    3. C step-down voltage for consumers
    4. D DC conversion
    💡 Explanation:

    They reduce HV distribution to LV utilization voltage at poles or pads.

  81. Q81 medium

    Power transformer impedance is designed mainly for

    1. A maximizing inrush
    2. B fault current limitation and system stability
    3. C eliminating regulation
    4. D zero copper loss
    💡 Explanation:

    Higher Z% limits short-circuit current but increases voltage regulation trade-off.

  82. Q82 easy

    Transformer oil serves as

    1. A only structural support
    2. B only flux path
    3. C insulation and coolant
    4. D only current carrier
    💡 Explanation:

    Mineral oil insulates windings and transfers heat from core and coils to tank walls.

  83. Q83 medium

    Dissolved gas analysis (DGA) in transformers detects

    1. A external lightning only
    2. B incipient insulation breakdown
    3. C meter calibration
    4. D tap position
    💡 Explanation:

    Gases like H2, CH4, C2H2 indicate overheating, partial discharge, or arcing in oil/paper.

  84. Q84 hard

    Winding hot-spot temperature limit for oil transformers is typically guided by

    1. A insulation aging (IEEE/IEC standards)
    2. B only ambient air
    3. C secondary current alone
    4. D tap number
    💡 Explanation:

    Hot-spot above 98-110°C accelerates cellulose aging; insulation life halves roughly every 6-7°C rise.

  85. Q85 medium

    FR3 or ester oil in transformers offers

    1. A lower insulation than mineral oil
    2. B no cooling function
    3. C increased flammability
    4. D higher fire point and biodegradability
    💡 Explanation:

    Natural ester fluids have fire points above 300°C and are environmentally friendlier.

  86. Q86 easy

    Transformer tank is earthed to

    1. A provide safety and fault current path
    2. B increase secondary voltage
    3. C block fault detection
    4. D eliminate Buchholz
    💡 Explanation:

    Grounding the tank protects personnel and ensures proper operation of protective devices.

  87. Q87 easy

    Lightning arrester on transformer protects against

    1. A steady state overload
    2. B low power factor
    3. C negative regulation
    4. D surge overvoltages
    💡 Explanation:

    Arresters clamp transient overvoltages from lightning or switching before they damage insulation.

  88. Q88 hard

    Surge impedance loading (SIL) relates to

    1. A transformer iron loss
    2. B CT ratio
    3. C transmission line reactive power balance
    4. D tap changer steps
    💡 Explanation:

    While line-related, transformer-line interface design considers SIL for voltage profile on long lines.