Switchgear and Protection MCQs 2026

80 questions with detailed answers · 54 from past papers · 8 quiz batches available

📚 Electrical Engineering 📄 54 Past-Paper Qs ✓ Free · No Login Needed
🎯 Mock Test

Read each question, think about the answer, then click Show Answer to reveal the correct option and explanation. Load 10 at a time so it stays manageable — perfect for one-topic study sessions on the bus or during a break.

Page 1 of 1 Questions 110 of 80
  1. Q1 Past Paper · PPSC/FPSC/NTS easy

    Fuse protects against

    1. A both overload and short circuit within its rating
    2. B only voltage regulation of line
    3. C only Ferranti effect
    4. D only motor synchronizing only
    💡 Explanation:

    Fuses respond to excessive current from overload or fault.

  2. Q2 Past Paper · PPSC/FPSC/NTS easy

    IDMT overcurrent relay characteristic means

    1. A operating time decreases as fault current increases above pick-up
    2. B time is fixed regardless of current
    3. C relay never operates on overload
    4. D pick-up is independent of plug setting
    💡 Explanation:

    Inverse definite minimum time relays give faster tripping for higher fault currents.

  3. Q3 Past Paper · PPSC/FPSC/NTS easy

    Instantaneous overcurrent element in a relay operates

    1. A only after 2 seconds always
    2. B only on reverse power
    3. C without intentional time delay once current exceeds setting
    4. D only when voltage is maximum
    💡 Explanation:

    Instantaneous units trip immediately when fault current exceeds threshold.

  4. Q4 Past Paper · PPSC/FPSC/NTS medium

    Directional overcurrent relay requires

    1. A only CT without PT
    2. B only fuse melting curve
    3. C both current and voltage inputs to determine power flow direction
    4. D only Buchholz gas pressure
    💡 Explanation:

    Directionality compares current angle relative to voltage reference.

  5. Q5 Past Paper · PPSC/FPSC/NTS medium

    Differential protection compares

    1. A only voltage magnitude at one bus
    2. B only frequency deviation only
    3. C only rotor speed of motor
    4. D current entering and leaving the protected zone
    💡 Explanation:

    Internal faults produce current imbalance detected by differential relay.

  6. Q6 Past Paper · PPSC/FPSC/NTS easy

    Buchholz relay is installed on transformers to detect

    1. A overflux due to high voltage only
    2. B differential current only on lines
    3. C distance to fault on cable
    4. D incipient faults producing gas in the oil
    💡 Explanation:

    Gas accumulation and oil surge indicate internal transformer faults.

  7. Q7 hard

    Restricted earth fault (REF) protection is sensitive to

    1. A phase faults on long transmission lines only
    2. B earth faults within the transformer differential zone near the star point
    3. C motor starting inrush only
    4. D Ferranti effect only
    💡 Explanation:

    REF uses CT and high-impedance relay for internal earth faults.

  8. Q8 Past Paper · PPSC/FPSC/NTS medium

    Distance relay measures apparent impedance to fault as

    1. A V/I seen by the relay
    2. B only current magnitude without voltage
    3. C only frequency
    4. D only zero-sequence voltage only
    💡 Explanation:

    Impedance relay infers fault location from measured V and I.

  9. Q9 Past Paper · PPSC/FPSC/NTS medium

    Plug setting multiplier (PSM) equals

    1. A time setting only
    2. B CT ratio only
    3. C breaking capacity only
    4. D fault current divided by relay pick-up current
    💡 Explanation:

    PSM determines operating point on IDMT curve.

  10. Q10 Past Paper · PPSC/FPSC/NTS medium

    Time setting multiplier (TSM) on an IDMT relay adjusts

    1. A CT primary turns only
    2. B the time dial to shift the inverse time curve
    3. C circuit breaker arc voltage only
    4. D motor slip only
    💡 Explanation:

    TSM selects desired grading with upstream/downstream relays.

  11. Q11 Past Paper · PPSC/FPSC/NTS easy

    Relay coordination on radial feeders ensures

    1. A all relays trip simultaneously always
    2. B only backup relay ever operates
    3. C the relay nearest the fault operates first
    4. D fuse never blows
    💡 Explanation:

    Time and current grading achieve selectivity.

  12. Q12 easy

    Numerical protection relays offer

    1. A only mechanical induction disc operation
    2. B programmable logic, self-test and event recording
    3. C no communication capability ever
    4. D mandatory oil immersion
    💡 Explanation:

    Microprocessor relays integrate multiple functions and communication.

  13. Q13 medium

    Electromechanical induction disc relay operating time depends on

    1. A only ambient temperature without current
    2. B only line length in km
    3. C only SIL of line
    4. D current magnitude and time dial setting
    💡 Explanation:

    Disc torque proportional to I² drives the inverse-time characteristic.

  14. Q14 Past Paper · PPSC/FPSC/NTS medium

    CT burden on relay must be kept within rating to avoid

    1. A increase of SIL
    2. B Ferranti voltage rise
    3. C saturation and loss of accuracy in protection
    4. D motor pull-out torque change
    💡 Explanation:

    Excessive burden causes CT saturation and relay maloperation.

  15. Q15 hard

    Overflux protection on transformers responds to

    1. A only differential current magnitude
    2. B only distance to fault
    3. C only negative-sequence current only on lines
    4. D V/f ratio exceeding allowable limit
    💡 Explanation:

    High V/f causes transformer core overheating.

  16. Q16 medium

    High-set instantaneous element is used to

    1. A replace all time-delayed elements always
    2. B accelerate clearance of close-in high-current faults
    3. C measure power factor only
    4. D control excitation of alternator only
    💡 Explanation:

    High-set units bypass delay for severe nearby faults.

  17. Q17 Past Paper · PPSC/FPSC/NTS hard

    Stability of differential relay during external faults requires

    1. A opening of all circuit breakers
    2. B CTs of adequate ratio and knee-point to avoid false differential current
    3. C zero load current always
    4. D leading power factor at receiving end only
    💡 Explanation:

    Matching CT performance prevents maloperation on through faults.

  18. Q18 Past Paper · PPSC/FPSC/NTS easy

    SF6 circuit breaker uses sulfur hexafluoride primarily because

    1. A it has high dielectric strength and excellent arc quenching capability
    2. B it is lighter than air only without arc benefit
    3. C it eliminates all fault current instantly without arc
    4. D it replaces the need for contacts
    💡 Explanation:

    SF6 gas cools and de-ionizes the arc efficiently at high pressure.

  19. Q19 Past Paper · PPSC/FPSC/NTS easy

    Vacuum circuit breaker extinguishes arc by

    1. A rapid dielectric recovery in high vacuum between contacts
    2. B oil spray on contacts only
    3. C compressed air blast only
    4. D long arc running in open air only
    💡 Explanation:

    Vacuum has no ionizable medium, aiding fast arc extinction.

  20. Q20 medium

    Air blast circuit breaker interrupts current by

    1. A SF6 liquefaction only
    2. B vacuum pumping only
    3. C high-pressure air jet axially along the arc
    4. D oil decomposition only
    💡 Explanation:

    Compressed air cools and stretches the arc in air-blast designs.

  21. Q21 Past Paper · PPSC/FPSC/NTS medium

    Oil circuit breaker relies on

    1. A vacuum alone without oil
    2. B arc decomposition of oil generating gas flow to extinguish arc
    3. C pure SF6 without tank
    4. D no arc interruption medium
    💡 Explanation:

    Oil CBs use oil as arc quenching and insulation medium.

  22. Q22 Past Paper · PPSC/FPSC/NTS hard

    Making capacity of a circuit breaker refers to

    1. A only load current at unity pf
    2. B maximum peak current it can close onto without excessive damage
    3. C only charging current of line only
    4. D only excitation current of alternator
    💡 Explanation:

    Making capacity relates to peak asymmetrical short-circuit closing duty.

  23. Q23 Past Paper · PPSC/FPSC/NTS easy

    Breaking capacity of a circuit breaker must

    1. A equal only full-load current
    2. B be less than load current always
    3. C exceed prospective fault level at the installation point
    4. D ignore short-circuit MVA always
    💡 Explanation:

    CB must safely interrupt maximum available fault current.

  24. Q24 hard

    Restriking voltage after current zero is the transient voltage appearing

    1. A only at transformer no-load
    2. B only during motor starting
    3. C across breaker contacts during interruption
    4. D only on DC systems without arc
    💡 Explanation:

    Recovery voltage stress determines successful interruption.

  25. Q25 hard

    Rate of rise of restriking voltage (RRRV) affects

    1. A successful arc extinction in oil and air break CBs
    2. B only cable charging current magnitude
    3. C only PID integral gain
    4. D only Buchholz gas volume only
    💡 Explanation:

    If RRRV exceeds dielectric recovery, restrike occurs.

  26. Q26 hard

    Current chopping in vacuum CB on low inductive current can cause

    1. A high transient overvoltages due to rapid current interruption
    2. B reduced insulation stress always
    3. C zero restriking voltage always
    4. D automatic reclosing failure only on fuses
    💡 Explanation:

    Sudden energy release in inductive circuits produces overvoltages.

  27. Q27 Past Paper · PPSC/FPSC/NTS medium

    Auto-reclosing on transmission lines attempts

    1. A never used on overhead lines
    2. B only on underground cables always without blocking
    3. C automatic closure after brief outage to restore permanent faults selectively
    4. D replacement of all relays
    💡 Explanation:

    Reclosing improves supply continuity for transient faults like lightning.

  28. Q28 medium

    Arc chutes in air break low-voltage breakers

    1. A increase fault level
    2. B lengthen and cool the arc for extinction
    3. C replace CT cores
    4. D measure distance to fault
    💡 Explanation:

    Splitters and chutes improve dielectric recovery in air.

  29. Q29 medium

    Minimum oil circuit breaker (MOCB) differs from bulk oil CB by

    1. A using smaller quantity of oil in interrupting chamber only
    2. B using no oil at all
    3. C operating only at EHV
    4. D having no moving contacts
    💡 Explanation:

    MOCB reduces oil quantity compared to bulk-oil designs.

  30. Q30 Past Paper · PPSC/FPSC/NTS medium

    SF6 breaker contact separation is accompanied by

    1. A high-pressure gas blast through the arc region
    2. B only vacuum creation in main tank
    3. C only oil jet without gas
    4. D only fuse wire melting
    💡 Explanation:

    Puffer or blast designs force SF6 through the arc column.

  31. Q31 Past Paper · PPSC/FPSC/NTS easy

    Circuit breaker rated voltage must match

    1. A only load current in amperes
    2. B only motor slip
    3. C only cable length in metres only
    4. D highest system voltage including insulation coordination margins
    💡 Explanation:

    Voltage rating ensures insulation withstand under normal and transient conditions.

  32. Q32 easy

    Operating mechanism of a CB may be

    1. A only manual fuse wire replacement
    2. B spring charged, pneumatic or hydraulic depending on design
    3. C only permanent magnet only without motion
    4. D only Buchholz float movement
    💡 Explanation:

    Stored-energy mechanisms provide fast and reliable operation.

  33. Q33 Past Paper · PPSC/FPSC/NTS medium

    Successful interruption requires current to reach

    1. A maximum peak always without zero
    2. B natural or forced zero with adequate dielectric recovery across contacts
    3. C DC offset only without decay
    4. D infinite frequency always
    💡 Explanation:

    Alternating current must pass through zero for AC interruption.

  34. Q34 Past Paper · PPSC/FPSC/NTS easy

    HRC fuse stands for

    1. A high reactive compensation
    2. B high rupturing capacity fuse
    3. C high resistance conductor
    4. D high relay coordination only
    💡 Explanation:

    HRC fuses safely interrupt high fault currents within rated capacity.

  35. Q35 Past Paper · PPSC/FPSC/NTS easy

    Cartridge type HRC fuse contains

    1. A only rewirable wire in open air
    2. B only oil without element
    3. C only vacuum interrupter
    4. D silver or copper element enclosed in silica sand filled tube
    💡 Explanation:

    Sand quenches arc and limits peak let-through current.

  36. Q36 Past Paper · PPSC/FPSC/NTS medium

    Cut-off current of a current-limiting fuse is

    1. A maximum instantaneous current reached before fuse clears
    2. B steady-state load current only
    3. C transformer magnetizing current only
    4. D motor full-load current only
    💡 Explanation:

    Fast melting limits prospective peak fault current.

  37. Q37 Past Paper · PPSC/FPSC/NTS easy

    Inverse time characteristic of a fuse means

    1. A time fixed for all currents
    2. B fuse never blows on overload
    3. C blow time increases with fault current
    4. D higher overcurrent clears in shorter time
    💡 Explanation:

    Fuse time-current curve is inverse like many overcurrent relays.

  38. Q38 Past Paper · PPSC/FPSC/NTS easy

    Rewirable Kit-Kat fuse is considered obsolete because

    1. A it has highest rupturing capacity
    2. B it has lower breaking capacity and poor discrimination
    3. C it is used on 400 kV lines
    4. D it replaces numerical relays
    💡 Explanation:

    Open rewirable fuses are unsafe for modern fault levels.

  39. Q39 medium

    Expulsion fuse used in outdoor distribution

    1. A uses arc energy to expel gases that extinguish the arc
    2. B requires SF6 tank always
    3. C operates only on DC
    4. D cannot be used outdoors
    💡 Explanation:

    Expulsion action blows arc products out of the tube.

  40. Q40 Past Paper · PPSC/FPSC/NTS medium

    Fuse coordination ensures

    1. A all fuses blow together always
    2. B breaker never operates
    3. C relay never picks up
    4. D fault is cleared by the smallest protective device upstream of the fault
    💡 Explanation:

    Selectivity minimizes outage area.

  41. Q41 Past Paper · PPSC/FPSC/NTS medium

    Current-limiting fuse reduces

    1. A line SIL to zero
    2. B excitation reactance of alternator
    3. C Bode gain margin only
    4. D I²t let-through energy seen by downstream equipment
    💡 Explanation:

    Limiting peak current protects cables and switchgear from thermal/mechanical stress.

  42. Q42 Past Paper · PPSC/FPSC/NTS easy

    Fuse rating in amperes indicates

    1. A maximum current the fuse can carry continuously without melting
    2. B minimum fault MVA only
    3. C distance relay reach only
    4. D PID proportional gain only
    💡 Explanation:

    Rated current must exceed normal load but clear on overcurrent.

  43. Q43 Past Paper · PPSC/FPSC/NTS easy

    Unlike a circuit breaker, a fuse

    1. A must be replaced after one fault operation
    2. B can reclose automatically always without inspection
    3. C measures impedance to fault
    4. D provides differential protection alone
    💡 Explanation:

    Fuses are single-shot protective devices.

  44. Q44 Past Paper · PPSC/FPSC/NTS medium

    Drop-out fuse cutout on distribution poles allows

    1. A visible open isolation when fuse carrier drops after operation
    2. B measurement of positive-sequence impedance only
    3. C automatic PID tuning
    4. D distance protection zone extension
    💡 Explanation:

    Drop-out action indicates blown fuse and isolates section.

  45. Q45 hard

    Striker fuse operates an indicator or tripping mechanism by

    1. A measuring V/f on transformer only
    2. B computing symmetrical components only
    3. C generating PWM for inverter only
    4. D mechanical movement when fuse element blows
    💡 Explanation:

    Striker pin provides remote indication or latch release.

  46. Q46 medium

    Selectivity between series fuses requires

    1. A identical ratings always
    2. B downstream fuse always slower
    3. C no coordination study
    4. D upstream fuse has higher rating or slower characteristic than downstream
    💡 Explanation:

    Time-current grading achieves fuse selectivity.

  47. Q47 Past Paper · PPSC/FPSC/NTS medium

    Sand filling in HRC fuse cartridge helps

    1. A increase fault current magnitude
    2. B quench the arc and absorb energy during interruption
    3. C reduce breaking capacity
    4. D eliminate the need for element
    💡 Explanation:

    Sand fuses and cools arc products rapidly.

  48. Q48 medium

    Fuse element material is often silver because

    1. A it never melts
    2. B it increases fault level
    3. C it has stable melting characteristics and good conductivity
    4. D it replaces CT saturation curve
    💡 Explanation:

    Silver provides predictable time-current behaviour.

  49. Q49 Past Paper · PPSC/FPSC/NTS easy

    Fortescue theorem states that

    1. A any unbalanced three-phase phasors can be resolved into three balanced sets
    2. B only positive sequence exists always
    3. C zero sequence requires no ground path
    4. D negative sequence rotates same as positive
    💡 Explanation:

    Positive, negative and zero sequence components sum to the original unbalanced system.

  50. Q50 Past Paper · PPSC/FPSC/NTS easy

    Positive sequence network is used for

    1. A only double line-to-ground faults without line
    2. B only DC circuits
    3. C only single-phase motors without neutral
    4. D balanced three-phase faults and normal balanced operation
    💡 Explanation:

    Balanced conditions involve only positive sequence.

  51. Q51 Past Paper · PPSC/FPSC/NTS medium

    Negative sequence components produce

    1. A reverse rotating field harmful to rotating machines
    2. B no effect on induction motors
    3. C only DC offset in transformers
    4. D only Ferranti voltage rise
    💡 Explanation:

    Negative sequence causes heating and torque pulsations in machines.

  52. Q52 Past Paper · PPSC/FPSC/NTS medium

    Zero sequence current flows only when

    1. A system is perfectly balanced always
    2. B delta winding carries zero sequence freely always
    3. C no ground exists anywhere
    4. D a return path exists for the zero sequence network (usually ground/neutral)
    💡 Explanation:

    Zero sequence requires grounded neutral or earth return.

  53. Q53 Past Paper · PPSC/FPSC/NTS medium

    Delta-connected transformer winding blocks

    1. A positive sequence only
    2. B zero sequence current from passing through the delta
    3. C all sequence networks equally
    4. D negative sequence only always on all designs
    💡 Explanation:

    Delta provides no zero-sequence path through the winding.

  54. Q54 Past Paper · PPSC/FPSC/NTS easy

    Single line-to-ground (SLG) fault involves

    1. A only positive sequence alone
    2. B all three sequence networks connected in series at fault point
    3. C only negative sequence alone
    4. D no zero sequence ever
    💡 Explanation:

    SLG is the most common fault and uses all sequence networks.

  55. Q55 Past Paper · PPSC/FPSC/NTS medium

    Line-to-line (LL) fault involves

    1. A zero sequence only
    2. B positive sequence only
    3. C positive and negative sequence networks in series
    4. D no sequence analysis needed
    💡 Explanation:

    LL faults have no zero-sequence component without ground involvement.

  56. Q56 Past Paper · PPSC/FPSC/NTS hard

    Sequence impedances Z1, Z2, Z0 of a static line typically satisfy

    1. A Z0 = 0 always
    2. B Z1 = Z2 and Z0 > Z1 for overhead lines with ground return
    3. C Z1 = Z0 always without ground wires
    4. D Z2 = infinity always
    💡 Explanation:

    Mutual coupling to ground makes zero-sequence impedance larger.

  57. Q57 Past Paper · PPSC/FPSC/NTS medium

    Unbalanced fault analysis using symmetrical components requires

    1. A only per unit change of base
    2. B only Bode plot of open-loop system
    3. C only SCR latching current test only
    4. D interconnection of sequence networks according to fault type
    💡 Explanation:

    Fault boundary conditions determine series/parallel sequence connections.

  58. Q58 hard

    Negative sequence heating in synchronous machines is severe because

    1. A no current flows in rotor
    2. B only stator heats without rotor effect
    3. C rotor sees double-frequency induced currents relative to forward field
    4. D machine runs as induction generator only
    💡 Explanation:

    Negative sequence creates reverse rotating field and rotor heating.

  59. Q59 hard

    Conversion from abc phase quantities to symmetrical components uses

    1. A only Laplace transform of DC signal
    2. B only Fourier series of square wave without phase
    3. C only PID derivative term
    4. D linear transformation with operator a = e^(j120°)
    💡 Explanation:

    Fortescue transformation matrix combines a operators.

  60. Q60 Past Paper · PPSC/FPSC/NTS medium

    Double line-to-ground (LLG) fault uses

    1. A positive sequence only
    2. B no zero sequence if ungrounded system only in some cases
    3. C DC component only
    4. D positive, negative and zero sequence networks interconnected
    💡 Explanation:

    LLG faults generally involve all three sequences on grounded systems.

  61. Q61 Past Paper · PPSC/FPSC/NTS easy

    Balanced three-phase load carries

    1. A equal negative and zero sequence always
    2. B only positive sequence current under normal conditions
    3. C only zero sequence
    4. D unbalanced sequence always
    💡 Explanation:

    Symmetry implies absence of negative and zero sequence.

  62. Q62 Past Paper · PPSC/FPSC/NTS medium

    Grounding system design affects primarily

    1. A zero sequence impedance and fault current magnitude for earth faults
    2. B only positive sequence only on delta systems without ground
    3. C only motor slip under load
    4. D only inverter switching frequency only
    💡 Explanation:

    Solid grounding lowers Z0 and increases SLG fault current.

  63. Q63 Past Paper · PPSC/FPSC/NTS medium

    Symmetrical components simplify fault studies because

    1. A they eliminate the need for per unit
    2. B they remove all resistances
    3. C sequence networks are often uncoupled except at fault point
    4. D they set all voltages equal
    💡 Explanation:

    Uncoupled sequence networks simplify analysis of unbalanced faults.

  64. Q64 hard

    Phase-a to ground voltage during SLG fault is

    1. A always equal for all phases
    2. B always maximum on faulted phase only without ground
    3. C approximately zero at fault location while other phases remain finite
    4. D undefined without sequence networks
    💡 Explanation:

    Faulted phase voltage collapses near fault; others may rise on ungrounded systems.

  65. Q65 Past Paper · PPSC/FPSC/NTS easy

    Impedance relay measures

    1. A only real power flow direction without voltage
    2. B only third harmonic only
    3. C only DC resistance of tower footing only
    4. D apparent impedance V/I to the fault point
    💡 Explanation:

    Measured impedance compared to reach setting determines trip.

  66. Q66 Past Paper · PPSC/FPSC/NTS medium

    Mho relay characteristic on R-X diagram is

    1. A a circle passing through origin oriented to forward faults
    2. B a vertical line only at all settings
    3. C a horizontal line at negative reactance only always
    4. D unrelated to impedance plane
    💡 Explanation:

    Mho element is inherently directional toward forward line faults.

  67. Q67 Past Paper · PPSC/FPSC/NTS medium

    Zone 1 distance protection typically covers

    1. A entire adjacent line without delay always
    2. B only transformer winding only
    3. C about 80% of protected line length instantaneously
    4. D only busbar differential zone
    💡 Explanation:

    Zone 1 underreach margin avoids overreach into adjacent equipment.

  68. Q68 Past Paper · PPSC/FPSC/NTS medium

    Zone 2 of distance relay provides

    1. A backup coverage beyond line end with intentional time delay
    2. B instantaneous tripping for all faults on adjacent lines without coordination
    3. C only reverse power protection
    4. D only REF on transformer
    💡 Explanation:

    Zone 2 reaches remote bus with grading delay.

  69. Q69 hard

    Zone 3 distance element acts as

    1. A instantaneous primary only without settings
    2. B far backup with longest time delay
    3. C motor stall protection only
    4. D Buchholz gas detection only
    💡 Explanation:

    Zone 3 covers remote lines/transformers as backup.

  70. Q70 Past Paper · PPSC/FPSC/NTS hard

    Power swing blocking in distance relays prevents

    1. A all internal transformer faults
    2. B all SLG faults always
    3. C fuse blowing on overload
    4. D tripping during stable power swings without fault
    💡 Explanation:

    Large impedance swings during stability events must not trip line.

  71. Q71 hard

    Carrier aided distance schemes use

    1. A only DC injection in rotor
    2. B only cable Murray loop only
    3. C communication between line ends for permissive or blocking tripping
    4. D only PID anti-windup only
    💡 Explanation:

    Pilot channels accelerate tripping for internal faults.

  72. Q72 Past Paper · PPSC/FPSC/NTS medium

    Reach setting of distance relay is specified in

    1. A only amperes of full-load current
    2. B only motor RPM only
    3. C ohms or percent of line positive-sequence impedance
    4. D only per unit sag only
    💡 Explanation:

    Reach defines impedance limit seen by relay for zone coverage.

  73. Q73 Past Paper · PPSC/FPSC/NTS hard

    Fault resistance can cause distance relay to

    1. A always overreach without exception
    2. B ignore all faults
    3. C measure only zero sequence
    4. D underreach compared to metallic fault assumption
    💡 Explanation:

    Arc and ground resistance add to measured impedance.

  74. Q74 hard

    Blinders on distance relays exclude

    1. A internal differential current only
    2. B transformer magnetizing inrush only without harmonic restraint
    3. C load encroachment into tripping characteristic
    4. D Ferranti effect on open end only
    💡 Explanation:

    Blinders prevent tripping on heavy load impedance points.

  75. Q75 hard

    Quadrilateral distance characteristic allows

    1. A only circular mho without resistance coverage adjustment
    2. B only instantaneous overcurrent without voltage
    3. C independent control of resistive and reactive reach
    4. D only fuse time-current curve only
    💡 Explanation:

    Quadrilateral suits long lines and high fault resistance.

  76. Q76 hard

    Permissive overreach transfer trip (POTT) uses

    1. A only local zone 3 without communication
    2. B only Buchholz relay contacts
    3. C received permissive signal from remote end to trip on internal fault
    4. D only open-loop PID step response
    💡 Explanation:

    Communication confirms remote detection before accelerated trip.

  77. Q77 Past Paper · PPSC/FPSC/NTS medium

    Step distance scheme applies

    1. A multiple impedance zones with increasing time delays
    2. B single instantaneous zone only always
    3. C only DC machine commutation only
    4. D only cable capacitance grading only
    💡 Explanation:

    Stepped zones provide primary and backup grading along line.

  78. Q78 Past Paper · PPSC/FPSC/NTS easy

    Distance relay is primarily applied on

    1. A low-voltage lighting circuits only
    2. B only battery rooms without CT
    3. C transmission lines and EHV feeders
    4. D only open-loop water level control only
    💡 Explanation:

    Impedance measurement suits long lines with significant Z.

  79. Q79 hard

    Voltage memory in distance relays helps

    1. A increasing Ferranti rise
    2. B maintaining directional and impedance measurement during close-in faults with voltage collapse
    3. C measuring motor slip only
    4. D replacing symmetrical components entirely
    💡 Explanation:

    Stored voltage polarizes relay when fault voltage is depressed.

  80. Q80 hard

    Switch-on-to-fault (SOTF) logic in distance protection allows

    1. A blocking of all zone 1 always
    2. B fast tripping when breaker closes onto a fault
    3. C disabling carrier channel permanently
    4. D measuring only third harmonic in transformer only without restraint
    💡 Explanation:

    SOTF detects fault present at closure without normal delay.